Busbar 120% rule calculator

Will the backfeed fit on this panel? The bar beside the panel shows how much of the busbar's allowance the main and the backfeed breaker use. If it doesn't fit, you get every way to make it work — and you can drag the backfeed breaker to see why its position matters.

The panel

NEC edition your AHJ adopted
A
From the panel's label, not the main breaker.
A
Backfeed
A
Maximum continuous output current, from the datasheet. Add together every inverter that backfeeds this panel, including a battery's. EV chargers and generators on a transfer switch don't count — they don't backfeed the busbar.
BUSBAR BUDGET FROM UTILITY MAIN 200 A BUS 200 A 60 A BACKFEED ▲▼ DRAG
Passes the 120% rule NEC 2020
Backfeed breaker you need
Largest backfeed this panel takes
    Have us draw it — $250
    Show the math with your numbers

    Section numbers follow the edition you pick — confirm the edition your jurisdiction adopted and any local amendments. Derating the main needs a load calculation that supports the smaller breaker. A design aid, not a sealed engineering document.

    What the 120% rule says

    When solar or a battery backfeeds a panel through a breaker, the busbar is fed from two directions at once: the utility through the main breaker, and the inverters through the backfeed breaker. The 120% rule allows the busbar to carry more than its rating in that situation, as long as:

    • the main breaker rating plus 125% of the backfeed — the continuous output current of every inverter feeding the panel, solar and battery — is no more than 120% of the busbar rating, and
    • the backfeed breaker sits at the opposite end of the busbar from the main.
    EditionSection
    NEC 2020 and 2023705.12(B)(3)(2)
    NEC 2017705.12(B)(2)(3)(b)
    NEC 2014 and earlier705.12(D)

    On a 200 A bus with a 200 A main, 120% of the bus is 240 A. Subtract the 200 A main and 40 A is left; divided by 1.25, the largest inverter output the panel takes is 32 A. For a fuller walkthrough with worked examples, see the 120% rule explained.

    Why the backfeed breaker goes at the opposite end

    With the utility at one end and the backfeed at the other, no single section of the busbar carries both currents at once — that is what makes the extra 20% safe. Plan checkers expect to see the backfeed breaker there, and the calculator always places it there, even when the panel passes on another rule.

    The other ways to comply

    • Within the busbar rating. If the main plus 125% of the backfeed fits within the bus rating itself, the 120% allowance isn't needed.
    • The sum rule. If every breaker in the panel except the main adds up to no more than the bus rating, including the backfeed breaker, the panel complies.
    • Derate the main. A smaller main breaker frees up room on the bus — only if a load calculation supports it.
    • Supply-side connection. Connecting ahead of the main takes the busbar out of the question, with utility and AHJ approval.
    • Upgrade the panel. The last resort, and usually the most expensive.

    Common questions

    How many amps can I backfeed on a 200 A panel with a 200 A main?
    Under the 120% rule, a 40 A breaker: 120% of 200 A is 240 A, minus the 200 A main. Because the breaker has to be 125% of the inverter current, that supports an inverter output of up to 32 A.
    Does the 120% rule apply to microinverters?
    Yes. Add up the output current of every microinverter on the circuit and treat the total like one inverter. The calculator does this when you choose Microinverters.
    Can I derate the main breaker to make room for solar?
    Often, yes. Replacing a 200 A main with a 175 A one raises the room for solar from 40 A to 65 A on a 200 A bus. It is only allowed if a load calculation for the home shows the smaller main is enough.
    Which NEC section is the 120% rule?
    705.12(B)(3)(2) in NEC 2020 and 2023, 705.12(B)(2)(3)(b) in NEC 2017, and under 705.12(D) in 2014 and earlier. Use the edition your jurisdiction adopted.